3100/3200 Series
Part No HA028651 Issue 3.0 Mar-06 97
16.3.5 To Calibrate Remote Setpoint Input
Connect a milli amp source to terminals HD and HE as shown.
Select
Conf Level as described in Chapter 2, then:-
Operation Do This Display View Additional Notes
Select the Calibration
List header
1. From any display press
as many times
as necessary until the ‘CAL’ page header is
displayed.
Scrolling display
CALIBRATIO N LIST
Select the Calibration
Phase
2. Press
to select ‘P H A S E
none
phase
Scrolling display
CALIBRATIO N phase
Set mA source for 4mA
Select the low
calibration point
3. Press
or
to choose ‘rm.CL
rm.CL
phase
Calibrate the
instrument to the low
calibration point
(4mA)
4. Press
to select ‘G O
5. Press
or
to choose ‘YES
Scrolling display
CALIBRATIO N start
The controller automatically calibrates to the
injected input. The display will show
busy
then
pass, (if calibration is successful.) or
FAIL’ if not. Fail may be due to incorrect
input. mA
Set mV source for 20mA
Select the high
calibration point
9. Press
to select ‘P H A S E
10. Press
or
to choose ‘rm.CH
11. Repeat 4 and 5 above to calibrate the high
point
rm.CH
phase
The controller will again automatically calibrate
to the injected input mV.
If it is not successful then ‘
FAIL will be
displayed
To calibrate the voltage input, connect a volts source to terminals HD (negative) and HF (positive). The procedure is the same as
described above but the calibration points are:-
Parameter Calibration Voltage
rm.VL
0 Volts
rm.VH
10 Volts
Copper cable
Current
Source
-
+
Controller
HD
HF
HE
-
+