13. Timer/Programmer
A timer can be configured to operate in one of four different modes. These can be selected in Level 3 or configuration level as:-
1.
Dwell timer
2.
Delay timer
3.
Soft start timer
4.
Programmer – this is an orderable option
Operation of the timer has been described in section 5.
13.1 Timer Parameters
The full list of all available parameters in configuration level is given in the following table.
TIMER LIST ‘tim e r’’
Name Scrolling
Display
Parameter Description Value Default Access
Level
none
Timer disabled
dwel
Dwell
deLY
Delayed switch on
SFST
Soft start
TM . C FG
TIMER
CONFIGURATI
ON
Timer type configuration
prog
Programmer
As order
code
L3
Hour
Hours HH:MM
TM . res
TIMER
RESOLUTION
To set the time units
Min
Minutes MM:SS
Conf
R/O L3
THRES
TIMER START
THRESHOLD
To set the maximum
deviation between SP
and PV before the timer
starts.
Dwell timer and
Programmer only
Off or 1 to 3000 Units above and below
setpoint
Off
L3
OFF
Control outputs go to zero %
DwEl
Control continues at SP1
SP2
Go to setpoint 2
ENd.T
TIMER END
TYPE
To determine the action
which takes place when
the timer has timed out.
Dwell timer and
Programmer only
res
Reset programmer
Conf
SS.SP
SOFT START
SETOINT
Sets the threshold below
which the power is
limited
SFST timer only
Controller input range 0 Conf
SS.PW R
SOFT START
POWER LIMIT
Sets the limit to the
power output during
start up
SFST timer only
0 to 100% 0 Conf
res
Reset
run
Running (counting)
hoLd
Running (hold)
T. STAT
TIMER STATUS
Timer status
end
Timed out
L3
servo
SERVO MODE
Defines the way in which
the programmer starts
and how it recovers from
Sp
Starts at SP1 (or SP2).
The program must be re-started
after a power failure.
sp