Eurotherm 3116 PID User's Guide Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 126
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
3100/3200 Series
32 Part No HA028651 Issue 3.0 Mar-06
6.1.3 To Select Access Level 3 or Configuration Level
Do This The Display You Should See Additional Notes
1. From any display press and hold
for more than 5 seconds
To Select Level 3
Lev 3
go to
0
CODE
The display will pass from the current operating level, for
example, Lev 1 to Lev 3 as the button is held down.
(If no button is then pressed for about 50 seconds the display
returns to the HOME display)
2. Press
or
to enter the
passcode for Level 3
3
code
The default code is 3:
If an incorrect code is entered the display reverts to ‘got o .
The controller is now in the level 3 will then revert to the
HOME display
3. When the LEV3 GOTO view is
shown, as in paragraph 1 above,
press
to select ‘Conf
To Select Configuration level
Conf
go to
0
CODE
Note:
must be pressed quickly before the controller
requests the code for level 3
4. Press
or
to enter the
passcode for Configuration level
4
code
Conf
The default code is 4:
If an incorrect code is entered the display reverts to
goto.
The controller is now in Configuration level will now show
Conf
5. Press and hold
for more than 3
seconds
6. Press
to select the required
level eg LEV 1
To Return to a Lower Level
Conf
go to
Lev1
go to
The choices are:
LEV 1 Level 1
LEV 2 Level 2
LEV 3 Level 3
ConF Configuration
It is not necessary to enter a code when going from a higher
level to a lower level.
Alternatively, press
and scroll to the A cces list
header, then press
to select the required level.
The display will then flash ‘ConF’ for a few seconds and the
controller will then go through its start up sequence, starting
in the level selected.
Do not power down while Conf is flashing. If a power down
does occur an error message will appear – see section 12.4
‘Diagnostic Alarms’
A special case exists if a security code has been
configured as ‘0’ If this has been done it is not necessary to
enter a code and the controller will enter the chosen level
immediately.
When the controller is in configuration level the
ACCESS list header can be selected from any view by
holding down the
button for more than 3 seconds.
Then press
again to select ‘ACCES’
Page view 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 125 126

Comments to this Manuals

No comments