3100/3200 Series
32 Part No HA028651 Issue 3.0 Mar-06
6.1.3 To Select Access Level 3 or Configuration Level
Do This The Display You Should See Additional Notes
1. From any display press and hold
for more than 5 seconds
To Select Level 3
Lev 3
go to
0
CODE
The display will pass from the current operating level, for
example, Lev 1 to Lev 3 as the button is held down.
(If no button is then pressed for about 50 seconds the display
returns to the HOME display)
2. Press
▲
or
▼
to enter the
passcode for Level 3
3
code
The default code is 3:
If an incorrect code is entered the display reverts to ‘got o ’.
The controller is now in the level 3 will then revert to the
HOME display
3. When the LEV3 GOTO view is
shown, as in paragraph 1 above,
press
▲
to select ‘Conf’
To Select Configuration level
Conf
go to
0
CODE
Note:
▲
must be pressed quickly before the controller
requests the code for level 3
4. Press
▲
or
▼
to enter the
passcode for Configuration level
4
code
Conf
The default code is 4:
If an incorrect code is entered the display reverts to
‘goto’.
The controller is now in Configuration level will now show
Conf
5. Press and hold
for more than 3
seconds
6. Press
▲
to select the required
level eg LEV 1
To Return to a Lower Level
Conf
go to
Lev1
go to
The choices are:
LEV 1 Level 1
LEV 2 Level 2
LEV 3 Level 3
ConF Configuration
It is not necessary to enter a code when going from a higher
level to a lower level.
Alternatively, press
and scroll to the A cces list
header, then press
to select the required level.
The display will then flash ‘ConF’ for a few seconds and the
controller will then go through its start up sequence, starting
in the level selected.
Do not power down while Conf is flashing. If a power down
does occur an error message will appear – see section 12.4
‘Diagnostic Alarms’
☺
A special case exists if a security code has been
configured as ‘0’ If this has been done it is not necessary to
enter a code and the controller will enter the chosen level
immediately.
☺ When the controller is in configuration level the
ACCESS list header can be selected from any view by
holding down the
button for more than 3 seconds.
Then press
again to select ‘ACCES’