3100/3200 Series
56 Part No HA028651 Issue 3.0 Mar-06
OP.LO
OUTPUT LOW
Adjust to limit the maximum cooling
power applied to the process or to
apply a minimum heating power
+
100.0%
0.0 (heat
only)
-100
(cool)
L3
MTR.T
MOTOR TRAVEL TIME
Set this value to the time that it takes
for the motor to travel from its fully
closed to its fully open position.
0.0 to 999.9 seconds
Note: In motorised valve control only the PB
and TI parameters are active. The TD
parameter has no effect on the control.
0.0 L3
D.BAND
CHANNEL 2 DEAD BAND
Period when no output is demanded
from either channel 1 or channel 2
Adjust, for example, to increase the
period when no heating or cooling
power is applied
Off or 0.1 to 100.0% of the cooling
proportional band
OFF
L3
HYST.H
HEATING HYSTERESIS -199.9 to 200.0 display units 1
HYST.C
COOLING HYSTERESIS -199.9 to 200.0 display units 1
L3
On/off
only
SAFE
SAFE OUTPUT POWER
To set the output level in a sensor
break (open circuit) condition
-100.0 to 100.0% limited by OP.HI and OP.LO 0.0% L3
none
Transfer between Auto/Manual/Auto
is bumpless
SteP
Transfer from Auto to Manual, the
output goes to a pre-set value (F.OP)
F. M O D
FORCED MANUAL OUTPUT MODE
Selects how the loop behaves on
transfer from Auto to Manual.
Transfer from Manual to Auto is
always bumpless.
Last
Transfer from Auto to Manual, the
output goes to the previously set
manual value
none
L3
Lin
Linear
OIL
Oil cooling
H20
Water cooling
C ool. t
NON-LINEAR COOLING TYPE
This selects an algorithm most suited
to the type of cooling. Typically used
in extruders.
Fan
Forced air cooling
As order
code
Conf
F. O P
FORCED OUTPUT
To pre-set a value for the Manual
output when F.MOD = STEP
-100.0 to 100.0% limited by OP.HI and OP.LO 0.0 L3
Auto
To select automatic operation
Man
To select manual operation
A-M
LOOP MODE – AUTO MANUAL OFF
see also section 3.4.3.
OFF
Control outputs inhibited
L3
No
lb r
LOOP BREAK STATUS
YES
Shows the current status of loop
break.
Read
only