3216 User Guide Part No. HA027985ENG Issue 2.0 May 04
ENG
39
6.9 Programmer
Model type CP is a controller which also contains a four segment setpoint programmer where each segment consists of a
controlled rate ramp to a target setpoint followed by a dwell at that setpoint. These values can be set by the user. The
program profile is shown in the diagram below.
Program RUNNING
Starts at
Current
WSP
OFF
RESET
RUN Digital O/P = trun
END Digital O/P = t.End
Temp
SP2 (70)
Time
SP1 (20)
Ramp to
TSP1 at
RMP1
End Type
Dwell
Ramp to
TSP2 at
RMP2
DWEL.1 DWEL.2 DWEL.3 DWEL.4
Ramp to TSP3
at RMP3
Ramp to TSP4
at RMP4
SP2 (servo from PV)
Off