6.4 Timer
A timer can be configured to operate in four different modes. These can be selected in Level 2 using the ‘TM.CFG’
parameter as:-
Dwell Timer
Delayed switch on timer
Soft start timer
Programmer if this has been ordered
There are four operating states:
1. Run. This starts the timer
2. Hold. This stops the timer at the elapsed time. It will start again from the elapsed time when Run is selected again.
3. Reset. This sets the timer back to zero. It can be run again from this state.
4. End cannot be set - it occurs automatically when the timer has counted down to zero
Run, Hold and Reset may be set through the front panel as described in section 6.8 or by the following methods:-
Edge trigger a suitably configured digital input
Power cycle the controller
Digital communications command
Selecting ‘T.STAT’ from the parameter list
Switching from Hold to Run through the front panel buttons is not allowable if the Hold status is forced by a logic input
or through Digital Communications.