5.4.3 Auto/Manual/Off Mode
Auto mode is the normal closed loop operation where the output is adjusted automatically by the controller in response
to a change in the input signal.
Manual mode means that the controller output power can be adjusted directly by the user. The input sensor is still
connected and reading the PV but the control loop is open. The current level of the power output is adopted at the
point of switch over from Auto to Manual. This is referred to as ‘Bumpless Transfer’. The power output can be increased
or decreased using the
or
buttons. Similarly, when Manual to Auto is selected the current manual output
power is taken and the controller will then take over control. If the controller is powered down it will resume the same
mode when powered up again.
Off mode can be selected or when using a timer configured to turn the power output off at the end of a timed period.
!
Manual operation must be used with care and the power level set must be chosen such that no damage can occur
to the process. The use of a separate ‘over-temperature’ controller is recommended.