Eurotherm 3216i User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
3200iSeries Indicators
Part No HA029006 Issue 5.0 Sept-12 15
4. Switch On
4.1 New Indicator
If the indicator is new and has not previously been
configured, or following a ‘Cold Start’ (section 6.5), it
will start up showing the ‘Quick Configuration’ codes.
This is a built in tool which enables you to configure
the input type and range, the output functions and
the display format.
!
Incorrect configuration can result in damage
to the process and/or personal injury and must be
carried out by a competent person authorised to do
so. It is the responsibility of the person
commissioning the instrument to ensure the
configuration is correct
The quick code consists of two ‘SETS’
of five characters.
The upper section of the display shows the set
selected, the lower section shows the five digits
which make up the set.
Adjust these as follows:-.
1. Press any button
. The first character will change
to a flashing ‘-‘.
2. Press
V
or
W
to change the flashing character
to the required code shown in the quick code
tables –see next page. Note: An
x indicates
that the option is not fitted.
3. Press
to scroll to the next character.
You cannot scroll to the next character until the
current character is configured.
To return to the first character press
.
4. When all five characters have been configured
the display will change to rng.hi followed by
rng.lo which allows range high and low limits to
be set.
5. The next press of
will select Set 2. Adjust
each character as described for Set 1.
6. When the last character has been entered press
again, the display will show . Continue
to press
if you wish to repeat the above
quick codes or press
V
or
W
to if you
are satisfied with the quick codes. The indicator
will then automatically go to the operator level
SET 1
K C H C 0
Input Type
G Strain gauge
32h8i only
Thermocouple
B Type B
J Type J
K Type K
L Type L
N Type N
R Type R
S Type S
T Type T
C Custom C
RTD
P Pt100
Linear (all units)
M 0-80mV
2 0-20mA
4 4-20mA
Linear 32h8i
0 0-10Vdc
1 1-5Vdc
3 2-10Vdc
6 0-5Vdc
Display
units
Decimal point
Temperature
0 nnnnn
(1)
X None 1 nnnn.n
(1)
C
o
C 2 nnn.nn
(1)
F
o
F 3 nn.nnn
(1)
K K 4 n.nnnn
(1)
P %
32h8I only:
0 Pa D L-m
1 mPa E %RH
2 Kpa G %O2
3 Bar H %CO2
4 mBar J %CP
5 PSI L V
6 Kg/cm
2
M Amp
7 mmWG R mA
8 inWG T mV
9 mmHG U Ohm
A Torr W ppm
B L-H Y RPM
Z m-s
PV Colour
(2)
32h8i only
G Green
R Red
C Colour change on Alarm.
Green to red
X Not applicable
Set 2 follows these
parameters
See next page
(1) Up to 2 decimal places on 3216i and 3204i
Up to 4 decimal places on 32h8i
(2) Colour change on top part of display only
Set 1 is followed Set this for the maximum
with RNG.H I display range required
Then Set this for the minimum
RNG . Lo
display range required
Home display
N PV only
A First Alarm SP only
1 PV + Alarm SP
2 PV + Alarm SP
(Read only)
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 87 88