3200iSeries Indicators
Part No HA029006 Issue 5.0 Sept-12 11
2.6.4 Digital Inputs A and B
Digital input A is not available in 32h8i/SG and
optionally available on 3216i
• Not isolated from the sensor input
• Switching: 12Vdc at 40mA max
• Contact open > 500Ω. Contact closed < 200Ω
• Input functions: Please refer to the list in the
quick codes.
2.6.5 Transducer Supply
In 32h8i/SG a 10Vdc supply is available as an
excitation voltage for a bridge type transducer
• Minimum load resistance 300Ω
• Isolated output 300Vac CATII
2.7 Indicator Power Supply
1. Before connecting the indicator to the power
line, make sure that the line voltage corresponds
to the description on the identification label.
2. Use copper conductors only.
3. The power supply input is not fuse protected.
This should be provided externally.
4. For 24V the polarity is not important.
• High voltage supply: 100 to 230Vac, +
15%,
48 to 62 Hz
• Low voltage supply:
24Vac, -15% +10%
24Vdc, -15% +20% +
5% ripple voltage
• Recommended external fuse ratings are as
follows:-
For 24 V ac/dc, fuse type: T rated 2A 250V
For 100 - 230Vac, fuse type: T rated
2A 250V.
2.8 Example Wiring Diagram
This shows 32h8i/SG connections for a strain gauge
bridge.
Safety requirements for permanently connected
equipment state:
• A switch or circuit breaker shall be included in
the building installation
• It shall be in close proximity to the equipment
and within easy reach of the operator
• It shall be marked as the disconnecting device
for the equipment.
Note: a single switch or circuit breaker can drive
more than one instrument.
Dig In
LA
C
Dig In B
LB
LC
+
-
Ext1
Ext2
N
32h8i/SG Indicator
R
CAL
Strain
Gauge
Internal
FET switch
Signal
- +
Cal
1
Txdcr
Supply
HF HE HD AC AE A
Fuse
- +
Cal
2
Cal
1
Ext
-
Ext
+
+
-
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
L
24V
24V
24
24
Line
Neutral
L
N