Eurotherm 3116 PID Installation Guide Page 94

  • Download
  • Add to my manuals
  • Print
  • Page
    / 140
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 93
Engineering Handbook 3200 Series
92 Part No HA028651 Issue 10.0 Dec -10
15.5 Parameter Modbus Addresses
Parameter
Mnemonic
Parameter Name Modbus Address
Decimal
PV.IN PV (Temperature) Input Value (see also Modbus address 203 which allows writes over Modbus to this variable). 1
TG.SP Target Setpoint.
NB – do not write continuously changing values to this variable. The memory technology used in this
product has a limited (100,000) number of write cycles. If ramped setpoints are required, consider using the
internal ramp rate function or the remote comms setpoint (Modbus address 26 )in preference.
2
MAN.OP Manual Output Value 3
WRK.OP Working Output 4
WKG.SP Working Setpoint (Read Only) 5
PB Proportional Band 6
CTRL.A
Control Action
0 = Reverse Acting
1 = Direct Acting
7
Ti Integral Time
(0 = No Integral Action)
8
Td Derivative Time
(0 = No Derivative Action)
9
RNG.LO Input Range Low Limit 11
RNG.HI Input Range High Limit 12
A1.--- Alarm 1 Threshold 13
A2.--- Alarm 2 Threshold 14
SP.SEL Active Setpoint Select
0 = Setpoint 1
1 = Setpoint 2
15
D.BAND Channel 2 Deadband 16
CB.Lo Cutback Low 17
CB.HI Cutback High 18
R2G Relative Cool/Ch2 Gain 19
MTR.T Motor Travel Time 21
T.STAT Timer Status
0 = Reset
1 = Run
2 = Hold
3 = End
23
SP1 Setpoint 1
NB – do not write continuously changing values to this variable. The memory technology used in this
product has a limited (100,000) number of write cycles. If ramped setpoints are required, consider using the
internal ramp rate function or the remote comms setpoint (Modbus address 26 )in preference.
24
SP2 Setpoint 2
NB – do not write continuously changing values to this variable. The memory technology used in this
product has a limited (100,000) number of write cycles. If ramped setpoints are required, consider using the
internal ramp rate function or the remote comms setpoint (Modbus address 26 )in preference.
25
Rm.SP
Remote (comms) setpoint. If selected using the remote setpoint selection (address 276 below, may also be
controlled using the instrument HMI or a digital input) then this is used as a setpoint providing a value has been
received within a window of about 5 seconds. If no value is received then the controller falls back to the currently
selected setpoint (SP 1 or SP 2) with an error indication. The Remote Setpoint may have a local trim (SP Trim,
address 27) added to it to compensate for variations in temperature in a particular zone.
This parameter is not saved when the instrument is switched off. It may be written to continuously over
communications without risk of damage to the instrument non-volatile memory.
26
LOC.t Local Trim – added to the remote setpoint to compensate for local temperature variations in a control zone. 27
MR Manual Reset 28
OP.HI Output High Limit 30
OP.LO Output Low Limit 31
SAFE Safe Output Value for Sensor Break or other fault conditions. 34
SP.RAT Setpoint Rate Limit Value (0 = no rate limit) 35
P.Err Calculated Error (PV-SP) 39
A1.HYS Alarm 1 Hysteresis 47
A2.HYS Alarm 2 Hysteresis 68
A3.HYS Alarm 3 Hysteresis 69
Page view 93
1 ... 93 94 95 ... 140

Comments to this Manuals

No comments